Insulation
Monitoring Relay
|
|
- Insulation Monitor 10-200 Kohm |
|
Insulation Monitoring Relay IR 195The Insulation Monitoring Relay IR 195 measures the network insulation resistance of ungrounded DC current networks to earth. Symmetrical earth faults are not detected, however this is of no significance for the fault conditions normally encountered.Threshold value RAN is factory set and non-variable. The IR 195 works according to the contact opening principle. Application of the aux. voltage causes the output relay to switch to the work position and a LED marked "ON" is lit,indicating that network insulation resistance RE>RAN. If the network insulation resistance drops below RAN the LED (ON) extinguishes, another LED marked "earth fault" is lit and the output relay deenergizes. With a jumper between terminal "1" and "2" IR 195 is programmed for memory, without link for hysteresis function. This link may be replaced by an external NC contact reset switch Correct functioning of the relay can be verified with a built-in test key. |
|
![]() |
|
Specifications |
Input Voltage |
24 VDC, 48 VDC, 110 VDC, 125 VDC, 220 VDC.( ±20%) |
Threshold RAN |
10 - 200 Kohm (Specify when order) |
Power Supply |
100 VAC, 110 VAC, 220 VAC |
Output Relay |
SPDT, 250V, 3A |
Ambient Temp. |
0 - 50 C. |
Connection |
Plug - in 11 pins socket |
Wiring |
Screw terminals on base socket |
Mounting |
Wall or DIN rail |
Dimension |
W50 X H70 X D130 mm. |
Ordering information |
Specify the following |
1. Input Voltage |
|
2. Threshold RAN |
|
3. Power Supply |
|
Example |
IR 195/125 VDC/50 Kohm/220 VAC. |