RTD Transmitter
RT 95

 

RTD Transmitter RT 95

- Linearizing for Pt100 sensor
- Programmable range
- Isolated input to output to Power Supply
- True lead length compensation

 

RTD Transmitter RT 95

          RTD transmitter RT 95 are compactly designed for converting the variations of resistance in a Pt 100 temperature sensor to a linearized and isolated DC. voltage or current output. They provide constant current excitation and true lead length compensation when used with a 3-wire RTD, which can be located at a considerable distance from the transmitter.

 

Diagram of RTD Transmitter Rt 95
 

Specifications

RTD input

Pt 100 DIN or JIS (3 wire type)

Lead wire resistance 5 ohm/wire max.

Rangeable zero from -100 C to +100 C

Rangeable span from 15 C to 500 C

Other types of RTD input available Cu 100, Pt 1000

Output

4-20 mA,0-20 mA (max. 1000 ohm load)

0-1V.,0-5V.,1-5V.,0-10V., (min. load 1000 ohm)

Linearity

< ± 0.2% of span

Isolation

500 Vac. Between input,output and power supply (1min. test)

Power supply

100 Vac.,110Vac.,220Vac.,24Vdc.

Ambient temperature

0-50 C

Connection

Plug-in 11 pins socket

Mounting

Wall or DIN rail

Dimension

W50 x H70 x D130mm.

Ordering information

Specify sensor type, input range, output, power supply

Example

RT 95/Pt 100/0-200 C/4-20 mA/220 Vac.