RTD Transmitter
|
||
![]() |
- Linearizing for Pt 100 sensor |
|
RTD Transmitter RT 98 RTD transmitter RT 98 are compactly designed for converting the variations of resistance in a Pt 100 temperature sensor to a linearized and isolated DC. voltage or current output. They provide constant current excitation and true lead length compensation when used with a 3 – wire RTD, which can be located at a considerable distance from the transmitter.
|
||
Specifications |
||
RTD input |
Pt 100 DIN or JIS (3 wire type) |
Lead wire resistance 5 ohm/wire max. |
|
Rangeable zero from -100 C to +100 C |
|
Rangeable span from 15 C to 500 C |
|
Other types of RTD input available Cu 100, Pt 1000 |
|
Output 1,2 |
4-20 mA,0-20 mA (max. 1000 ohm load) |
0-1V.,0-5V.,1-5V.,0-10V., (min. load 1000 ohm) |
|
Linearity |
< ± 0.2% of span |
Isolation |
500 Vac. Between input,output and power supply (1min. test) |
Power supply |
100 Vac.,110Vac.,220Vac.,24Vdc. |
Ambient temperature |
0-50 C |
Connection |
Plug-in 11 pins socket |
Mounting |
Wall or DIN rail |
Dimension |
W50 x H70 x D130mm. |
Ordering information |
Specify sensor type, input range, output1,output2, power supply |
Example |
RT 98/Pt 100/0-200 C/4-20 mA/1-5 Vdc/220 Vac. |