Square Root Transmitter |
|
|
||
| The Square Root Transmitter ST 20 is square root computer. It is designed to solve the equation Q = C √ΔP where ΔP is the differential pressure across an orifice, and C is a constant relating the orifice plate to engineering units. Because ST 20 does not use the curve segment, biased diode technique, it provides accuracy and resolution limited only by the stability and calibration of the orifice plate and its transmitter. The ST 20 output is a standard process current or voltage signal that is linearly proportional to flow. | ||
Specifications |
|
| Input – Output Equation | % Output = √100 x %Input |
| Input | 0-20mA., 4-20mA., 0-10V., 0-5V., 1-5V. |
| Output | 0-20mA., 4-20mA., 0-10V., 0-5V., 1-5V. |
| Span | Adjustable + 10% of full scale output |
| Zero | Adjustable + 5% of full scale output |
| Linearity | + 0.5% of span |
| Power Supply | 24 VDC. |
| Ambient Temperature | 0 – 50 °C |
| Mounting | DIN Rail |
| Dimension | W20 x H100 x D118 mm. |
| Ordering Information | Specify Input, Output |
| Example | ST20/4-20 mA/4-20mA |