Thermocouple
Transmitter
|
||
![]() |
- Wide progammable input range |
|
![]() |
||
Specifications |
||
Thermocouple input |
Rangeable within type J 0-600 C |
Rangeable wihtin type K 0-1200 C |
|
Rangeable wihtin type L 0-600 C |
|
Rangeable wihtin type R 0-1700 C |
|
Rangeable wihtin type S 0-1700 C |
|
(Units are rangeable within type of thermocouple supplied |
|
but not between different thermocouple types) |
|
Cold junction compensation range |
0-50 C |
Burn Out thermocouple |
Upscale drive standard |
Linearity |
< ± 0.25% of span (for J,K thermocouples) , |
< ± 0.5% of span (for other types) |
|
Output |
2 wire 4-20mA (loop powered) |
Ambient drift |
< ± 0.02%/ C of span |
Power supply |
12-35V DC. (loop powered) |
Output load resistance |
600 Ohm at 24 VDC. (50 Ohm/V above 12 VDC. |
Isolation voltage |
500 VAC. input/output isolation (1min. test) |
Maximum output current |
< 26 mA |
Operating temperature |
0-60 C |
Operating ambient humidity |
90 % RH max. |
Mounting |
DIN or EN rail |
Ordering information |
TT 37 / thermocouple type / temperature range |
Example |
TT 37 / K / 0-500 C |