Thermocouple
Transmitter
|
||
- Programmable range |
||
Thermocouple Transmitter TT 95 The thermocouple's signal is linearized and cold-junction compensated to provide an isolated and linearized DC. voltage or current output. Typically the Thermocouple Transmitter TT 95 interfaces with recording, monitering or controlling instruments
|
||
![]() |
||
Specifications |
||
Thermocouple input |
Rangeable within type J 0~800 C |
Rangeable within type K 0~1200 C |
|
Rangeable within type L 0~600 C |
|
Rangeable within type R 0~1700 C |
|
Rangeable within type S 0~1700 C |
|
Rangeable within type T -200~200 C |
|
Cold junction compensation |
0-50 C |
Burn out thermocouple |
Upscale drive standard |
Linearity |
< ± 0.2% of span |
Output |
4-20 mA,0-20 mA(max. 1000 ohm load) |
0-1 V,0-5 V,1-5 V.(min 1000 ohm load) |
|
Power supply |
100 Vac.,110 Vac.,220 Vac.,24 Vdc. |
Ambient temperature |
0-50 C |
Isolations voltage |
500Vac(1 min.) between input, output, power supply |
Connection |
Plug-in 11 pins socket |
Mounting |
Wall or DIN rail |
Dimension |
W50 x H70 x D130 mm. |
Ordering information |
Specify thermocouple type, input range, output, power supply |
Example |
TT 95/K/0-400 C/4-20 mA/220 Vac |