Var Transducer
VAR 95

 

Var Transducer VAR 95

          Var Transducers VAR 95  are used to convert single or three phase unbalance load reactive power into a proportional load independent DC. output. Based fully electronic Time-Division Multiplication measuring principle, the reactive power of a network with any power factor range are linearly produced by Var Transducers output.

 

Calibration var of rated output

Connection

V=110V

V=220V

V=380V

I=1A

I=5A

I=1A

I=5A

I=1A

I=5A

Single Phase

±100var

±500var

±200var

±1000var

-

-

3phase,3wire

±200var

±1000var

±400var

±2000var

±600var

±3000var

3phase,4wire

±200var

±1000var

±400var

±2000var

±600var

±3000var

Note. V= Line voltage

Equation to calculated measuring range
Measuring range = Calibration var x PT ratio x CT ratio
Example 3phase,3wire, PT 220V/110V, CT 250/5A, Calibration var = 1000W
Measuring range = 1000 x (220/110) x (250/5) = 100 Kvar.


Specifications

Connecttion

1 phase,3 phase 3 wire, 3 phase 4 wire

Input voltage

110 VAC.,220 VAC.,380 VAC.( Line voltage for 3 phase )

Input current

1 A.,5 A.

Frequency

50 Hz.

Power consumption

< 0.2VA for input current, <0.4VA for voltage input

Output

 

Output

Max. load

Output

Min. load

-1 ~ +1mA

10 Kohm

-10 ~ +10mV

500 ohm

4 ~ 20 mA

600 ohm

-100 ~ +100mV

500 ohm

- 1 ~ +1V

500 ohm

-10 ~ +10V

2 Kohm

-5 ~ +5V

1 Kohm

1 ~ 5V

1 Kohm

Linearity

< ¾ 0.5% of span

Power supply

110 VAC,220 VAC.

Operating temperature

0-50 C

Wiring

Screw terminals

Mounting

Wall mount

Dimension

W132 x H132 x D162 mm. .

Ordering information

Specify connection , input voltage , input current ,

output power supply

Example

VAR 95/3 phase 4 wire/380 VAC./5A/4-20 mA/220 VAC