Watt Transducer
|
||
-
High accuracy |
||
Watt Transducers WAT 95 Watt
Transducers WAT 95 are used to convert single or three phaseunbalance
load active power into a proportional load independent DC. Output.Based
fully on electronic Time-Division Multiplication measuring principle,the
true power of a network with any power factor range are linearly produced
by Watt Transducer output. |
||
![]() |
||
| Calibration watt of rated output |
||||||
| Connection |
V=110V |
V=220V |
V=380V |
|||
| I=1A |
I=5A |
I=1A |
I=5A |
I=1A |
I=5A |
|
| Single Phase |
100W |
500W |
200W |
1000W |
- |
- |
| 3phase,3wire |
200W |
1000W |
400W |
2000W |
600W |
3000W |
| 3phase,4wire |
200W |
1000W |
400W |
2000W |
600W |
3000W |
Note. V= Line voltage Equation to calculated measuring range |
Specifications |
Connecttion |
1 phase,3 phase 3 wire, 3 phase 4 wire |
Input voltage |
110 VAC.,220 VAC.,380 VAC.( Line voltage for 3 phase ) |
Input current |
1 A.,5 A. |
Frequency |
50 Hz. |
Power consumption |
< 0.2VA for input current, <0.4VA for voltage input |
Output |
Output |
Max. load |
Output |
Min. load |
|
0-1mA |
10Kohm |
0-10mV |
500 ohm |
||
4-20 mA |
600 ohm |
0-100mV |
500 ohm |
||
0-1V |
500 ohm |
||||
0-10V |
2Kohm |
||||
0-5V |
1Kohm |
||||
1-5V |
1Kohm |
Linearity |
< ± 0.5 % of span |
Power supply |
110 VAC,220 VAC. |
Operating temperature |
0-50 C |
Wiring |
Screw terminals |
Mounting |
Wall mount |
Dimension |
W132 x H132 x D162 mm. |
Ordering information |
Specify connection , input voltage , input current , output power supply |
Example |
WAT 95/3 phase 4 wire/380 VAC./5A/4-20 mA/220 VAC |